Instructions: To better prepare for your next linear lighting system installation, use our voltage drop calculator to customize the different aspects of the system such as wire gauge and run lengths between fixtures.
This does not apply to the VESTA ( internal driver).
Resistance | Amps | VD (Calculation) | Voltage | Wire Gauge (Typical Sizes) | % Voltage Drop (Do not exceed 3%) |
---|---|---|---|---|---|
25.67 | 3.96 | 2.033064 | 22.966936 | 24 | 8.13% |
16.14 | 3.96 | 1.278288 | 23.72172 | 22 | 5.11% |
10.15 | 3.96 | 0.80388 | 24.19612 | 20 | 3.22% |
6.385 | 3.96 | 0.505692 | 24.494308 | 18 | 2.02% |
4.016 | 3.96 | 0.3180672 | 24.6819328 | 16 | 1.27% |
2.525 | 3.96 | 0.19998 | 24.80002 | 14 | 0.80% |
1.588 | 3.96 | 0.1257696 | 24.8742304 | 12 | 0.50% |
0.999 | 3.96 | 0.0791208 | 24.9208792 | 10 | 0.32% |
0.628 | 3.96 | 0.0497376 | 24.9502624 | 8 | 0.20% |
0.395 | 3.96 | 0.031284 | 24.968716 | 6 | 0.13% |